15 Replacement of Parts

Diagram 15.6

14385

Diagram 15.7

14402

SECURING

SCREW

SECURING

SCREW

DRAIN

POINT

HEAT

EXCHANGER

(with the burner and flow pipe

removed for clarity)

Remove the heat exchanger

Undo the screws securing the flanged elbow on the top right

hand side of the heat exchanger and remove the retaining clip

from the flanged elbow, see diagram 15 5.
Remove retaining clip from the flanged elbow on the bottom of

the heat exchanger, see diagram 15.4.
Remove screws securing the heat exchanger, one on top and

one underneath the heat exchanger, see diagram 15.6.
Lift up heat exchanger slightly to disengage it from its hanging

bracket.
Remove the heat exchanger by pulling forward, then pulling

to the right to disengage the return pipe and tilting backwards

to ease removal complete with sump. Discard the heat

exchanger and flanged elbows.

Remove the burner

Remove the six flanged nuts and two studs that secure the

burner, note that the two studs also hold the fan clamping

bracket, see diagram 15.7.
Taking great care not to damage the surface of the burner.
NOTE: Replace the burner gasket and follow the tightening

sequence when re-fitting the burner, see diagram 15.7.
NOTE: Fit all replacement gaskets and seals when re-fitting

parts.
Refer to Section 12.
Fill the boiler heating system.
Re-pressurise (sealed sysem only)
Check for any leaks.
Vent all air from the system.
Test for gas tightness, earth continuity, polarity, short circuit

and resistance to earth.
Light the boiler and carry out functional checks.