13 Servicing

13.6. Heat Exchanger

NOTE: If the functional checks did not indicate poor

combustion then it is not necessary to service this

component.
Remove loose debris from inside the heat exchanger using a

soft brush and vacuum cleaner.
Carefully flush by spraying water into the heat exchanger, any

remaining debris should pass through the condensate trap

(Ensure the water is kept away from electrical components).

13.7 Condense Trap and Siphonic Drain

The condensate trap and siphonic drain does not normally

need servicing unless material deposits exceed beyond the

service fill level, see diagram 13.13.
To clean the condense trap remove the sump and rinse with

water.

Diagram 13.13

14089

SECURING

NUTS (6)

BURNER

FAN CLAMPING

BRACKET

Diagram 13.12

14410

14397

13.8 Casing panel seal check

NOTE: If the functional checks did not indicate poor

combustion then it is not necessary to service this

component.
Check the condition of the seal and replace if worn or

damaged.
To replace remove the old seal and thoroughly clean the

casing surfaces. Fit the new seals, these are supplied to the

correct lengths and are in four pieces, for use on the sides,

top and bottom.

13.9 Service Completion

Re-check the combustion as described at the beginning of this

section.

On completion of the service the “Benchmark” Service Record

should be completed.