TCD 600 ALARM OUTPUT CONNECTION DIAGRAMS

FIGURE 10B

ELECTRICAL CONNECTIONS (continued...)

29/31

30/32

TCD 600

To PLC Input

VDC Common

VDC

(See Specifications for

maximum voltage.)

R

(See Note.)

User Supplied

User Supplied

NOTE: The minimum value of resistor (R) is 10 x VDC.

29/31

30/32

TCD 600

VDC Common

VDC

(See Specifications for

maximum voltage.)

(See Note.)

User Supplied

User Supplied

NOTE: The minimum value of Resistor (R) is equal to VDC

divided by the maximum current limit of the Indicator.

R

External Indicator

29/31

30/32

TCD 600

VDC Common

VDC

(See Specifications for

maximum voltage.)

(See Notes.)

User Supplied

User Supplied

NOTES: 1. Be sure the current requirement of the External Coil does not

exceed the capability of the alarm output (

2. Any inductive load, such as a relay coil, must have a 1N4002,

or equivalent, diode across it as shown.

External

Coil

1N4002

Alarm Output Tied to External Indicator

Alarm Output Tied to PLC Input.

Alarm Output Tied to External Inductive Coil