3.1.4 Talk

Time

This programming sequence sets the maximum time allowed for conversation when the entry system
places a call to the resident. The talk time can be set from 1 second up to 255 seconds (4 minutes,
15 seconds) and is entered as a three-digit number. For example, to set a talk time of 20 seconds,
enter 020 in step 3. The talk time set here does not affect the telephone numbers that are
programmed under directory codes 0, 00, 000, 0000 and 1, 01, 001, 0001. The talk time for these
two directory codes are factory set to the maximum. Phone numbers programmed under these
directory codes should be reserved for management or emergency phone numbers that generally
require longer conversations.

Factory setting for talk time = 60 seconds.

1. Press



and enter the four digit MASTER CODE

BBBB

(beep).

2. Enter three digits for talk time (seconds)

BBB

(001-255) then press

(beep).

3. Press



TOGETHER to end this programming step (beeeeeep).

3.1.5 Tone Open Numbers

These steps will program the tone open numbers for relays 1 and 2. You will need to enter a four-
digit number (see chart below) to set the relay functions. If a function is not desired, enter # in place
of a number. For example, if you want the relay to have a momentary activation function only, and
you want the relay to activate when the number 9 is pressed, enter



in step 3. Do not

duplicate tone open numbers, i.e., don’t set relay 1, and 2 tone-open numbers to 9.

Factory setting is: Relay 1 = 9876, Relay 2 = 5432.

1. Press



and enter the four-digit MASTER CODE

BBBB

(beep).

2. Press



to set relay 1 or



to set relay 2 tone numbers.

3.

Enter the four-digit tone open number code

BBBB

then press

(beep).

4.

Repeat steps 2 and 3 to set the other relay tone open numbers.

5. Press



TOGETHER to end this programming step (beeeeeep).

DIGIT FUNCTION

1

Momentary activation. Relay will activate for the programmed strike time (3.1.3).

2

Relay hold. Relay will activate and remain activated until commanded to release.

3

Relay release. Deactivates the relay hold command.

4

Relay hold 1-hour. Relay will activate for 1-hour and then will automatically deactivate itself.