Basic information
12
BC3100
Electrical data
The electrical data specific to the field bus is listed in this chapter. The
following table shows the data in an overview:
Technical data’s
BC3100
Number of bus terminals
64
Digital peripheral signals
256 inputs/outputs
Analog peripheral signals
128 inputs/outputs
Maximum number of bytes
512 bytes I and 512 bytes O
Programming possibility
via programming interface (TwinCAT BC) or Profibus-DP (TwinCAT)
Program size
approximately 3000 plc statements
Program memory
32 kbytes
Data memory
32 kbytes
Permament flags
512 bytes
Run time system
1 PLC task
PLC cycle time
approximately 3 ms for 1000 commands (including K-bus I/O cycle)
Programming languages
IL, LAD, CSF, SFC, ST
Field bus interface
Profibus-DP
Baud rates
automatic baud rate detection up to 12 MBaud
Bus connection
1 x D-sub connector, 9-pole, with screen
Power supply
24 V DC, (20...29 V DC)
Input current
70 mA + (total K-bus current/4
500 mA max.
Power-on current
2.5 x continuous current
Recommended fuse
≤ 10 A,
K-bus power supply up to
1750 mA
Power contact voltage
24 V DC max.
Power contact current load
10 A max.
Diaelectric strength
500 Vrms (Power contact/supply voltage/field bus)
Operating temperature
0°C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95%, no condensation
Vibration/shock resistance
in accordance withIEC 68-2-6 / IEC 68-2-27
EMC/emssion
in accordance with EN 50082 (ESD, Burst) / EN 50081
Installed position
any
Degree of protection
IP20
Current consumption on the
K-Bus
For operation of the K-bus electronics, the bus terminals require energy
from the K-bus that is supplied by the bus terminal controller. Refer to the
catalog or the corresponding data sheets of the bus terminals for details of
the K-bus current consumption. In doing so, pay attention to the maximum
output current of the bus terminal controller that is available for powering
the bus terminals. Using a special power supply terminal (KL9400), power
can be fed back into the K-bus at any chosen point. If you wish to use a
power supply terminal, please contact Beckhoff’s technical support.