Electrical data

The electrical data specific to the field bus is listed in this chapter. The
following table shows the data in an overview:

Technical data’s

BC3100

Number of bus terminals

64

Digital peripheral signals

256 inputs/outputs

Analog peripheral signals

128 inputs/outputs

Maximum number of bytes

512 bytes I and 512 bytes O

Programming possibility

via programming interface (TwinCAT BC) or Profibus-DP (TwinCAT)

Program size

approximately 3000 plc statements

Program memory

32 kbytes

Data memory

32 kbytes

Permament flags

512 bytes

Run time system

1 PLC task

PLC cycle time

approximately 3 ms for 1000 commands (including K-bus I/O cycle)

Programming languages

IL, LAD, CSF, SFC, ST

Field bus interface

Profibus-DP

Baud rates

automatic baud rate detection up to 12 MBaud

Bus connection

1 x D-sub connector, 9-pole, with screen

Power supply

24 V DC, (20...29 V DC)

Input current

70 mA + (total K-bus current/4
500 mA max.

Power-on current

2.5 x continuous current

Recommended fuse

≤ 10 A,

K-bus power supply up to

1750 mA

Power contact voltage

24 V DC max.

Power contact current load

10 A max.

Diaelectric strength

500 Vrms (Power contact/supply voltage/field bus)

Operating temperature

0°C ... +55°C

Storage temperature

-25°C ... +85°C

Relative humidity

95%, no condensation

Vibration/shock resistance

in accordance withIEC 68-2-6 / IEC 68-2-27

EMC/emssion

in accordance with EN 50082 (ESD, Burst) / EN 50081

Installed position

any

Degree of protection

IP20


Current consumption on the
K-Bus

For operation of the K-bus electronics, the bus terminals require energy
from the K-bus that is supplied by the bus terminal controller. Refer to the
catalog or the corresponding data sheets of the bus terminals for details of
the K-bus current consumption. In doing so, pay attention to the maximum
output current of the bus terminal controller that is available for powering
the bus terminals. Using a special power supply terminal (KL9400), power
can be fed back into the K-bus at any chosen point. If you wish to use a
power supply terminal, please contact Beckhoff’s technical support.