PROFIBUS bus terminal controller BC3100

36

BC3100

Byte No

Description

Byte 0

Terminal No (1-64)

Byte 1

Channel No (1-4)

Byte 2

PLC process image, low byte address

Byte 3

PLC process image, high byte address

Byte 4

PLC process image bit address

Byte 5

Analog terminals: status byte of the terminal
Digital terminals: bit 1: short circuit channel 0

short circuit channel 1

Byte 6

(reserved for expansions)

Byte 7

(reserved for expansions)


The PLC process image addresses are entered only if the corresponding
tables have been transferred (see Table 80 in the bus coupler).

Diagnostics messages of
the bus coupler

Besides the diagnostics messages of the terminals, there are also 2
diagnostics messages of the bus coupler.

Byte No

Description

Byte 0

0

Byte 1

0

Byte 2

Initialisation error

Byte 3

Terminal bus error

Byte 4

Invalid test on bus reset or invalid terminal number in the event of a
terminal bus error

Byte 5

Invalid terminal number on bus reset

Byte 6

First terminal number not supported

Byte 7

0

Byte No

Description

Byte 0

0

Byte 1

255

Byte 2

UserPrmData error
0: No error
1: Reserved
2: Input or output data too long
3: Invalid byte or word of the UserPrmData

Byte 3

First invalid byte or word of the UserPrmData

Byte 4

CfgData error
0: No error,
1: Not enough CfgData,
2: Invalid CfgData byte,
3: Error generating the DP process image
4: Error generating the PLC process image (BC3100 only)

Byte 5

Byte 4 = 2:
First invalid byte of the CfgData (0 - 63)
Byte 4 = 3:
0: Maximum input or output length exceeded
2: Compile buffer in the case of the DP process image is too small
Byte 4 = 4:
0: Maximum input or output length exceeded
2: Compile buffer in the case of the PLC process image is too small
(BC 3100 only)

Byte 6

0

Byte 7

0

Initialisation

error


Description

Bit 0

Error reading out the EEPROMs