Profibus bus terminal controller bc3100, Parameterization – BECKHOFF BC3100 User Manual

Page 29

Advertising
background image

PROFIBUS bus terminal controller BC3100

BC3100

29

PROFIBUS bus terminal controller BC3100


Parameterization

Besides the parameterization in the DP standard, manufacturer-specific
operating parameters (User_Prm_Data) can also be transferred with the
Set_Prm service. These are distinguished by the fact that they are
transferred once from the master to the slave during establishment of the
connection. User_Prm_Data overwrites the settings that have been made
by way of the configuration interface. If these settings are not to be
overwritten, User_Prm_Data must not be sent. The User-Prm_Data of the
bus terminal controller BC3100 is based on the following structure:

Byte No.

Description

Byte 0

Bit 0: Start-Bit monitoring on (0) / off (1)
Bit 1: Stop-Bit monitoring on (0) / off (1)
Bit 2: Watchdog time base 10ms (0) / 1ms (1)
Bit 3-5: 0 (reserved for expansions)
Bit 6: Fail_Safe off (0) / on (1)
Bit 7: DPV1-MSAC_C1 connection disabled (0) / enabled (1)

Byte 1

0 (reserved for expansions)

Byte 2

0 (reserved for expansions)

Byte 3

0 (reserved for expansions)

Byte 4

0 (reserved for expansions)

Byte 5

Bit 1: diagnostics via 2-byte diagnostics interface (1)
Diagnostics via DP diagnostics (Slave_Diag) (0)
Bit 0, 2-7: 0 (reserved for expansions)

Byte 6

0 ( reserved for expansions)

Byte 7

Bit 0: auto reset on the terminal bus in the event of an error on
(1)/off(0)
Bit 1: automatic terminal diagnostics on(1)/off(0)
Bit 4: diagnostics of digital terminals is mapped to the process
image (0)/ is not mapped to the process image (1)
Bit 2,3, 5-7: 0 (reserved for expansions)

Byte 8

0 (reserved for expansions)

Byte 9

Bit 0: 1
Bit 1: 1
Bit 2: 0
Bit 3: data format for auto configuration: INTEL (0)/MOTOROLA(1)
Bit 4: 0
Bit 5: 1
Bit 6: 1
Bit 7: 0

Byte 10

Bit 0,1: reaction to field bus error/termination of DP data
exchange/Clear_Data
1: affiliated terminal bus outputs change to 0
2: affiliated terminal bus outputs remain unchanged
Bit 2,3: Reaction to terminal bus error
1: affiliated DP inputs change to 0
2: affiliated DP inputs remain unchanged
Bit 4-7: 0 (reserved for expansions)

Byte 11

Max. DP diagnostic data length (value range 16, 24, 32, 40, 48, 56,
64)



Advertising