PROFIBUS-DP basics

26

BC3100

the terminating resistor will vary, which may affect the data transfer.

Configuration of the masters

The Profibus bus terminal controller operates with two different process
images: the PLC process image to which all bus terminals or only some of
the bus terminals configured on the one specific BC3100 are assigned, as
well as the Profibus DP process image to which a part of the bus terminals
can be assigned. For details of parameterization and configuration, please
refer to the chapter entitled Profibus bus terminal controller BC3100.

The Profibus master exchanges a coherent input and output data block
with each Profibus coupler/controller. The master assigns the bytes from
this data block from the addresses of the process image. The
COMProfibus software supports configuration when using the PLC master
of the IM308-C. Use the manufacturers' corresponding tools for other
masters (see also chapter entitled Master device file and type file).

Support files for master configuration:

Master / Software

Remarks

File

IM308-B

COMET200

BK3000TD.200

IM308-C

COMProfibus

Bitmaps

BUSKLEMN.BMP
BUSKLEMS.BMP

English

Language-

independent

BK3000AD.200
BK3000AE.200
BK3000AX.200

General

(for BK30XX)

BK30BECF.GSD
BK3010.GSD

General

(for BK31XX)

BK31BECE.GSD
BK3110.GSD

General

(for BC3100)

BC3100.GSD


Example for the master
IM308-C
Interfacing for PLC Simatic
S5

In an example, we will show what settings have to be made in
COMProfibus to configure the Profibus master IM308-C.
Diverse bus terminals are connected to a BC3100:

In this example, the bus terminal controller's PLC program requires 5 bytes
of input signals (DP outputs of the master) and returns 6 bytes of output
signals (DP inputs of the master).

The corresponding entries for the identifiers can be selected conveniently
by way of the order number. The following window shows the selected
identifier: