BECKHOFF BC3100 User Manual

Page 31

Advertising
background image

PROFIBUS bus terminal controller BC3100

BC3100

31

Byte No.

Description

Byte 30

Bit 0,1:
0: 61. Terminal is assigned to the DP process image
2: 61. Terminal is assigned to the PLC process image and
mapped compactly (only with useful data)
3: 61. Terminal is assigned to the PLC process image and
mapped completely
Bit 2,3:
0: 62. Terminal is assigned to the DP process image
2: 62. Terminal is assigned to the PLC process image and
mapped compactly (only with useful data)
3: 62. Terminal is assigned to the PLC process image and
mapped completely
Bit 4,5:
0: 63. Terminal is assigned to the DP process image
2: 63. Terminal is assigned to the PLC process image and
mapped compactly (only with useful data)
3: 63. Terminal is assigned to the PLC process image and
mapped completely
Bit 6,7:
0: 64. Terminal is assigned to the DP process image
2: 64. Terminal is assigned to the PLC process image and
mapped compactly (only with useful data)
3: 64. Terminal is assigned to the PLC process image and
mapped completely

Bytes 31-36

Reserved for expansions

Byte 37

Initial address in the PLC input process image as from which
plc inputs are to be transferred as DP outputs (high byte)

Byte 38

Initial address in the PLC process image as from which PLC
inputs are to be transferred as DP outputs (low bytes)

Byte 39

Length of the PLC inputs that are to be transferred as DP
outputs

Byte 40

Initial address in the PLC output process image as from which
PLC outputs are to be transferred as DP Inputs (high bytes)

Byte 41

Initial address in the PLC output process image as from which
PLC outputs are to be transferred as DP inputs (low byte)

Byte 42

Length of the PLC outputs that are to be transferred as DP
inputs

Byte 43

Nominal PLC cycle time (in ms, value range: 1 - 255)

Byte 44

Background execution time (in ms, value range: 1 -255)

Bytes 45,46

Length of the remanant flags (as from MB0, which are stored in
the NOVRAM, value range: 1 - 512)


If no bus terminal controllers assume the last programmed value. Remark:
the default setting of the User_Prm_Data can be taken from the GSD file.