34

BC3100


The DP configuration data for the various terminals is as follows:

Terminal

DP Configuration data

KL3002, KL3012,
KL3022, KL3032,
KL3042, KL3052,
KL3062, KL3202,

KL3302

Channel 1 Channel 2
A: 0x50 0x50
B: 0xB2 0xB2
C: 0xC0 0x00 0x82 0xC0 0x00 0x82
D: 0x40 0x82 0x40 0x82
E: 0xC0 0x00 0x81 0xC0 0x00 0x81
Total
F: 0x51
G: 0xF2

KL3004, KL3014,
KL3024, KL3034,

KL3064

Channel 1 Channel 2 Channel 3 Channel 4
A: 0x50 0x50 0x50 0x50
B: 0xB2 0xB2 0xB2 0xB2
C: 0xC0 0x00 0x82 0xC0 0x00 0x82 0xC0 0x00 0x82 0xC0 0x00 0x82
D: 0x40 0x82 0x40 0x82 0x40 0x82 0x40 0x82
E: 0xC0 0x00 0x81 0xC0 0x00 0x81 0xC0 0x00 0x81 0xC0 0x00 0x81
Total
F: 0x53
G: 0xF5

KL4002,

KL4012, KL4022,

KL4032

Channel 1 Channel 2
A: 0x60 0x60
B: 0xB2 0xB2
C: 0xC0 0x82 0x00 0xC0 0x82 0x00
D: 0xC0 0x81 0x00 0xC0 0x81 0x00
E: 0x80 0x82 0x80 0x82
Total
F: 0x61
G: 0xF2

KL4004, KL4014,

KL4024, KL4034

Channel 1 Channel 2 Channel 3 Channel 4
A: 0x60 0x60 0x60 0x60
B: 0xB2 0xB2 0xB2 0xB2
C: 0xC0 0x82 0x00 0xC0 0x82 0x00 0xC0 0x82 0x00 0xC0 0x82 0x00
D: 0xC0 0x81 0x00 0xC0 0x81 0x00 0xC0 0x81 0x00 0xC0 0x81 0x00
E: 0x80 0x82 0x80 0x82 0x80 0x82 0x80 0x82
Total
F: 0x63
G: 0xF5

KL1501

B: 0xB4
G: 0xF2

KL2502

B: 0xB2
G: 0xF2

KL5001

A: 0xD1
B: 0xB4
C: 0xC0 0x00 0x84
D: 0x40 0x84
E: 0xC0 0x00 0x83

KL5101

B: 0xB5
G: 0xF2

KL6001, KL6011,

KL6021

B: 0xB5
G: 0xF2


Auto mapping of the PLC
inputs and outputs

Once all terminals belonging to the DP process image have been defined,
the PLC input and output area mapped into the DP process image now
also has to be taken into account in DP configuration data.








In doing so, use must be made of the following identifiers, any number of