3 technical data – BECKHOFF EK1914 User Manual

Page 16

Advertising
background image

Product description

14

EK1914

3.3 Technical data

Product designation

EK1914

Task within the EtherCAT system

coupling of EtherCAT Terminals (ELxxxx) to
100BASE-TX EtherCAT networks

Protocol / Baud rate

EtherCAT Device Protocol / 100 MBaud

Cable length between two Bus Couplers

max. 100 m (100BASE-TX)

Transmission medium

at least Ethernet CAT-5 cable

Bus connection

2 x RJ45

Supply voltage for the EK1914 (PELV)

24 V

DC

(-15%/+20%)

Number of standard inputs

4

Number of standard outputs

4

Number of safe inputs

2

Number of safe outputs

2

Status display

16 LEDs

Reaction time
(Read input/write to E-bus)

typically: 4 ms,
maximally: see error reaction time

Error reaction time

watchdog time

Signal voltage “0”, standard inputs

-3 V ... 5 V (EN 61131-2, type 1/3)

Signal voltage “1”, standard inputs

11 V ... 30 V (EN 61131-2, type 3)

Input filter, standard inputs

500 µs

Input current, standard inputs

typically 3 mA (EN 61131-2, type 3)

Output current per standard output

max. 0.5A

Output current of the clock outputs

typically 10 mA, max. 15 mA

Output current per safe output

max. 500 mA, min. 20 mA

Actuators

when selecting actuators please ensure that the test
pulses from the safe outputs do not lead to actuator
switching.

Cable length between
sensor/actuator and Bus
Coupler

(unshielded)

100 m max.(at 0.75 or 1 mm²)

(shielded)

100 m max.(at 0.75 or 1 mm²)

Input process image

8 byte

Output process image

8 byte

E-bus power supply (5 V)

max. 500 mA
(in case of higher current consumption, please use
additional

EL9410

power feed terminals!)

Power contacts (PELV)

max. 24 V

DC

, max. 4 A

Current consumption (excluding current
consumption of the sensors/actuators and further
terminals on the E-bus)

typically 72 mA

Power loss of the Bus Coupler

typically 1.8 W without connected sensors/actuators

Electrical isolation (between the channels)

no

Electrical isolation (between the channels and the
E-bus)

no

Electrical isolation (between the EtherCAT
connections and the channels/E-bus)

yes

Insulation voltage (between the EtherCAT
connections and the channels/E-bus, under
common operating conditions)

insulation tested with 500 V

DC

Dimensions (W x H x D)

approx. 44 mm x 100 mm x 68 mm

Weight

approx. 123 g