2 diagnostic objects – BECKHOFF EK1914 User Manual

Page 39

Advertising
background image

Operation

EK1914

37

4.4.2 Diagnostic objects

The CoE objects 800E

hex

display further diagnostic information.

CAUTION

Do not change CoE objects!

Do not make any modifications to the CoE objects of the TwinSAFE Bus Coupler! Any
modifications (e.g. using the TwinCAT system manager) of the CoE objects would
permanently set the Bus Coupler to the Fail-Stop state.

Index 800E

hex

: diagnostic objects - safe inputs

Index

Name

Meaning

Flags

Default
value

800E:0

Diag

The following sub-indices contain detailed
diagnostic information.

RO

800E:0A

Sensor test error

Bit

Error during the sensor test

RO

0

1

bin

Error at input 1

0

bin

1

1

bin

Error at input 2

0

bin

800E:0B

Error during two-
channel evaluation

Bit

Error during the contiguous evaluation of
two channels, i.e. the two channels
contradict each other.

RO

0

1

bin

Error in the first input pair

0

bin

800E:0C

Error in the safety
mat operating
mode: input pair not
identical

Bits

Error in the input pair

RO

1, 0

11

bin

Error in the first input pair

00

bin

800E:0D

Error in the safety
mat operating
mode: external
supply

Bit

Error in the test pulses in the safety mat
operating mode; i.e. the Bus Coupler has
detected an external supply.

RO

0

1

bin

Error at input 1

0

bin

1

1

bin

Error at input 2

0

bin

Advertising