BECKHOFF EK1914 User Manual

Page 40

Advertising
background image

Operation

38

EK1914

Index 800E

hex

: diagnostic objects - safe outputs

Index

Name

Meaning

Flags

Default
value

800E:0E

Diagnosis µC1

Valu
e

Description

RO

5

Cross-circuit output 1 and output 2

0

6

Cross-circuit output 1 and output 2

0

10

Overvoltage

0

11

Undervoltage

0

21...
27

Error when testing the field voltage
switches

0

30...
33

Start-up of the output circuit failed

0

101

External supply 0 V output 1, detected
with set output

0

102

External supply 24 V output 1

0

103

External supply 0 V output 2, detected
with set output

0

104

External supply 24 V output 2

0

800E:0F

Diagnosis µC2

Valu
e

Description

RO

201

External supply 0 V output 1, detected
with set output

0

202

External supply 24 V output 1

0

203

External supply 0 V output 2, detected
with set output

0

204

External supply 24 V output 2

0

Note

Differing diagnostic messages possible

Due to the variable order or execution of the test series, diagnostic messages differing
from those given in the table above are possible.