BECKHOFF EK1914 User Manual

Page 35

Advertising
background image

Operation

EK1914

33

Parameter overview

PrmName

Meaning

Values

FSoE_Address

DIP switch address

1 to 4095

Standard outputs
active

In addition the safe output can be switched off
from the standard PLC. The safe output is linked
with the standard logic signal AND.

true / false

Testing of outputs
active

Test pulses for the outputs are activated

true / false

Error acknowledge
active

True:

Bus Coupler errors lead to a reset of the
TwinSAFE connection (error code 14 (0x0E)).
This error code is shown in the diagnostic data for
the connection until the user acknowledges it via
ErrAck in the TwinSAFE group.

False (Default):

Bus Coupler errors can only be reset by switching
the power supply off and back on again.

true / false

Sensor test channel
1 active

The clock signal of the “Clock output safe input 1”
connection is tested at the “Safe input 1”
connection.

true / false

Sensor test channel
2 active

The clock signal of the “Clock output safe input 2”
connection is tested at the “Safe input 2”
connection.

true / false

Logic channel 1
and 2

Logic of channels 1 and 2

- single logic

- asynchronous repetition
OSSD (sensor test must be
switched off)

- any pulse repetition
OSSD (sensor test must be
switched off)

- short cut is no module
fault

Store Code

This parameter is required for the TwinSAFE
Restore Mode

-

Project CRC

This parameter is required for the TwinSAFE
Restore Mode

-

Identity

These parameters are used internally only.

-

Detected Modules

These parameters are used internally only.

-