3 possible causes of diagnostic messages – BECKHOFF EK1914 User Manual

Page 41

Advertising
background image

Operation

EK1914

39

4.4.3 Possible causes of diagnostic messages

Diagnostics

Possible cause

Remedial actions

Diag 2 LED

800E:0E / 800E:0F
set to:

5.6 or greater than
100

If parameter Testing of outputs active is switched
on:

Faulty test pulses.

Cause: external supply or cross-circuit.

Eliminate cross-circuit or
external supply.

Faulty test pulses.

Cause: parallel routed cables with high capacitive
coupling and dynamized signals, possibly also in
common cables

Isolate lines and lay in
separate non-metallic
sheathed cable.

Create a distance
between the non-metallic
sheathed cables.

Cause: current exceeds the limit of 500 mA.

Select actuator
accordingly.

Current < 500 mA

Irrespective of whether the parameter Testing of
outputs active
is switched on:

The output voltage lies below the permissible
voltage range (24 V -15%/+20%).

A possible cause is a short-circuit at the output or
e.g. a voltage drop at the instant of switching.

Eliminate short-circuit.

Design power supply
accordingly.

Check supply lines for
voltage drop.

EMC faults

Take suitable EMC
measures

Internal defect

Exchange Bus Coupler

Diag 2 LED

800E:0E / 800E:0F
set to: 11

Voltage on the power contacts too low.

Increase Bus Coupler
supply voltage and reset
error display by power-on
reset of the Bus Coupler

EMC faults

Take suitable EMC
measures

Internal defect

Exchange Bus Coupler