EK1914

4.1.6 Pin assignment of the EK1914

Terminal
point

Signal

Description

1

+24V

Supply voltage Us

2

In1

Standard input 1

3

In3

Standard input 3

4

Out 1

Standard output 1

5

Out 3

Standard output 3

6

Safe In1

Clock output safe input 1

7

Safe input 1

8

Safe Out 1

Safe output 1

9

0V

Supply voltage Us

10

In2

Standard input 2

11

In4

Standard input 4

12

Out 2

Standard output 2

13

Out 4

Standard output 4

14

Safe In2

Clock output safe input 2

15

Safe input 2

16

Safe Out 2

Safe output 2

Note

Configurable safe inputs

The safe inputs 1 and 2 can be connected alternatively to normally closed contacts or
normally open contacts. The corresponding analysis is carried out in the safety PLC.

Note

Test pulses of the safe outputs

When selecting actuators, please ensure that the EK1914 test pulses do not lead to
actuator switching or a diagnostic message from the EK1914.