Operation

40

EK1914

Diagnostics

Possible cause

Remedial actions

Diag 2 LED

800E:0E /
800E:0F set to:
10

Field potential too high.

Voltage on the power contacts too high.

Decrease Bus Coupler supply
voltage and reset error display
by power-on reset of the Bus
Coupler

Voltage briefly too high due to external
influences, such as switching contactors off.

Use an R/C or diode-based
protective circuit on the
actuators

EMC faults

Take suitable EMC measures

Internal defect

Exchange Bus Coupler