5 maintenance, 1 cleaning, 2 service life – BECKHOFF EK1914 User Manual

Page 43

Advertising
background image

Operation

EK1914

41

4.5 Maintenance

The TwinSAFE Bus Couplers are maintenance-free!

WARNING

Observe the specified environmental conditions!

Please ensure that the TwinSAFE Bus Couplers are only stored and operated under
the specified conditions (see technical data).


If the Bus Coupler is operated outside the permitted temperature range it will switch to Global Fault state.

4.5.1 Cleaning

Protect the TwinSAFE Bus Couplers from unacceptable soling during operation and storage!

If the TwinSAFE Bus Couplers were subjected to unacceptable soiling they may no longer be operated!

WARNING

Have soiled Bus Couplers checked!

Cleaning of the TwinSAFE Bus Coupler by the user is not permitted!

Please send soiled Bus Couplers to the manufacturer for inspection and cleaning!

4.5.2 Service life

The TwinSAFE Bus Couplers are designed for a service life of 20 years.

Due to the high diagnostic coverage within the lifecycle no special proof tests are required.

The TwinSAFE Bus Couplers bear a date code, which is composed as follows:

Date code: CW YY SW HW

Legend:

CW:

Calendar week of manufacture

YY:

Year of manufacture

SW:

Software version

HW:

Hardware version

Example: Date code

27 14 01 00

Calendar week:

27

Year:

2014

Software version:

01

Hardware version:

00


In addition the TwinSAFE Bus Couplers bear a unique serial number.

Advertising