2 bus terminals, 3 e-bus, 4 power contacts – BECKHOFF EL6930 User Manual

Page 11

Advertising
background image

System description

EL6930

9

2.1.2

Bus Terminals

Mechanical data

Mechanical data

Bus Terminal

Material

polycarbonate, polyamide (PA6.6).

Dimensions (W x H x D)

12 mm x 100 mm x 68 mm or 24 mm x 100 mm x 68 mm

Installation

on 35 mm mounting rail (EN50022) with locking

Attachable by

double slot and key connection

Connection technology

Connection technology

Bus Terminal

Wiring

cage Clamp

®

spring-loaded system

Connection cross-section

0.08 mm

2

... 2.5 mm

2

, stranded wire, solid wire

Fieldbus connection

E-bus

Power contacts

up to 3 blade/spring contacts

Current load

10 A

Rated voltage

depends on Bus Terminal type

2.1.3

E-bus

The E-bus is the data path within a terminal strip. The E-bus is led through from the Bus Coupler through
all the terminals via six contacts on the terminals' side walls.

2.1.4

Power contacts

The operating voltage is passed on to following terminals via three power contacts. Terminal strip can be
split into galvanically isolated groups by means of potential feed terminals as required. The power feed
terminals play no part in the control of the terminals, and can be inserted at any locations within the
terminal strip.

Advertising