Operation

EL6930

39

4.2.10.1 EL6930 project design limits

TwinSAFE connections

max. 127 (with 1 or 2 bytes safe user data per connection)
max. 50 connections per TwinSAFE group
Only 16 connections of an EL6930 can be slave connections.

PROFIsafe connections

1 PROFIsafe slave connection (must always be the first connection
in the configuration)

Supported hardware for EL6930
TwinSAFE connections

EL1904 (all)
EL2904 (all)
EL2902 (all)
KL1904 (from 2008)
KL2904 (from 2008)
KL6904 as slave (from 2008)
AX5805 (all)

Safe data per connection

up to 14 bytes safe user data (correspondingly lower total number
of connections)

TwinSAFE blocks

255 max.

TwinSAFE groups

32 max.

Standard PLC inputs

dynamic up to 255-bit

Standard PLC outputs

dynamic up to 255-bit

Note

TwinSAFE connection

Only one TwinSAFE connection between two TwinSAFE terminals is possible.
Between two EL6900/EL6930 logic terminals a connection can be set up that may
contain up to 14 bytes safe user data.