4.1.5

Tested EL2904 devices

The following list contains devices that were tested together with the EL2904 TwinSAFE terminal. The
results only apply for the current device hardware version at the time of testing. The tests were carried out
in a laboratory environment. Modifications of these products cannot be considered here. If you are unsure
please test the hardware together with the TwinSAFE terminal.

Manufacturer

Type

Comment

Beckhoff

AX5801

TwinSAFE Drive option card: safe restart lock

Beckhoff

AX2000 Option AS

safe restart lock

Siemens

SIRIUS Serie S00
3RT1016-1BB42

Contactor

Telemecanique LP1K09

Contactor


The tests were carried out as function tests only. The information provided in the respective manufacturer
documentation remains valid.

Note

Recommended protective circuits

We recommend R/C or diode-based protective circuits for these devices.

Varistor-based protective circuits should not be used.

4.1.6

Tested EL1904 devices

The following list contains devices that were tested together with the EL1904 TwinSAFE terminal. The
results only apply for the current device hardware version at the time of testing. The tests were carried out
in a laboratory environment. Modifications of these products cannot be considered here. If you are unsure
please test the hardware together with the TwinSAFE terminal.

Manufacturer Type

Comment

SICK

C4000

Safety light curtain

SICK

S3000

Safety laser scanner

Wenglor

SG2-14ISO45C1

Safety light grids

Leuze

lumiflex ROBUST 42/43/44

Safety light barriers

Schmersal

BNS250-11ZG

Safety switch

ifm

GM701S

Inductive safety sensor

The tests were carried out as function tests only. The information provided in the respective manufacturer
documentation remains valid.