2 diagnostic object – BECKHOFF EL6930 User Manual

Page 54

Advertising
background image

Operation

52

EL6930

4.4.1.5

Diag 4 LED (red) if Diag 3 LED (red) is not lit.

If the Diag 3 LED is not lit, the Diag 4 LED indicates the state of the TwinSAFE terminal.

Diag 3 LED Diag 4 LED: Flashing Code

Meaning

off

1 flash pulse (uniform flashing)

Function block error in one of the TwinSAFE
groups

off

2 flash pulses (2 pulses with longer
pause in between)

Communication error in one of the TwinSAFE
groups

off

3 flash pulses (3 pulses with longer
pause in between)

Function block and communication error in
one of the TwinSAFE groups

off

Steadily lit

Supply voltage or internal temperature of the
terminal outside the permissible range. The
diagnostic object FA00

hex

provides you with

more detailed information.

4.4.2 Diagnostic object

The CoE object FA00

hex

displays further diagnostic information.

CAUTION

Do not change CoE objects!

Do not change any of the CoE objects in the TwinSAFE terminals! Any modifications
(e.g. using the TwinCAT system manager) of the CoE objects would permanently set
the terminals to the Fail-Stop state.

Index FA00

hex

: Diagnostic object

Index

Name

Meaning

Flags

Default
value

FA00:0

Diag

RO

FA00:03

Temper
ature
error

0005

hex

Maximum temperature exceeded

RO

0000

hex

0006

hex

Temperature fell below minimum

0007

hex

Temperature difference between the measuring
points exceeded

Supply
error

0101

hex

max. supply voltage µC1 exceeded

0102

hex

max. supply voltage µC2 exceeded

0103

hex

voltage fell below max. supply voltage µC1

0104

hex

voltage fell below max. supply voltage µC2