2 diagnostic object – BECKHOFF EL6930 User Manual
Page 54
![background image](/files/774855/content/doc054.png)
Operation
52
EL6930
4.4.1.5
Diag 4 LED (red) if Diag 3 LED (red) is not lit.
If the Diag 3 LED is not lit, the Diag 4 LED indicates the state of the TwinSAFE terminal.
Diag 3 LED Diag 4 LED: Flashing Code
Meaning
off
1 flash pulse (uniform flashing)
Function block error in one of the TwinSAFE
groups
off
2 flash pulses (2 pulses with longer
pause in between)
Communication error in one of the TwinSAFE
groups
off
3 flash pulses (3 pulses with longer
pause in between)
Function block and communication error in
one of the TwinSAFE groups
off
Steadily lit
Supply voltage or internal temperature of the
terminal outside the permissible range. The
diagnostic object FA00
hex
provides you with
more detailed information.
4.4.2 Diagnostic object
The CoE object FA00
hex
displays further diagnostic information.
CAUTION
Do not change CoE objects!
Do not change any of the CoE objects in the TwinSAFE terminals! Any modifications
(e.g. using the TwinCAT system manager) of the CoE objects would permanently set
the terminals to the Fail-Stop state.
Index FA00
hex
: Diagnostic object
Index
Name
Meaning
Flags
Default
value
FA00:0
Diag
RO
FA00:03
Temper
ature
error
0005
hex
Maximum temperature exceeded
RO
0000
hex
0006
hex
Temperature fell below minimum
0007
hex
Temperature difference between the measuring
points exceeded
Supply
error
0101
hex
max. supply voltage µC1 exceeded
0102
hex
max. supply voltage µC2 exceeded
0103
hex
voltage fell below max. supply voltage µC1
0104
hex
voltage fell below max. supply voltage µC2