3 technical data – BECKHOFF EL6930 User Manual

Page 16

Advertising
background image

Product description

14

EL6930

3.3 Technical data

Product designation

EL6930

Number of inputs

0

Number of outputs

0

Status display

4 diagnostic LEDs

Minimum cycle time

approx. 500 µs

Error reaction time

watchdog times

Watchdog time

min. 1 ms, max. 60,000 ms

Input process image

Dynamic according to the TwinSAFE configuration in
the TwinCAT System Manager

Output process image

Dynamic according to the TwinSAFE configuration in
the TwinCAT System Manager

EL6930 supply voltage

24 V

DC

(-15%/+20%)

Current consumption from the E-bus

approx. 188 mA

Power dissipation of the terminal

typically 1 W

Dimensions (W x H x D)

12 mm x 100 mm x 68 mm

Weight

approx. 50 g

Permissible ambient temperature (operation)

0

to +55

Permissible ambient temperature
(transport/storage)

-25

to +70

Permissible air humidity

5 % to 95 %, non-condensing

Permissible air pressure
(operation/storage/transport)

750 hPa to 1100 hPa

Climate category according to EN 60721-3-3

3K3

Permissible level of contamination

level of contamination 2
(comply with the chapter Cleaning)

Impermissible operating conditions

TwinSAFE terminals must not be used under the
following operating conditions:

under the influence of ionizing radiation

in corrosive environments

in an environment that leads to
unacceptable soiling of the Bus Terminal

Vibration / shock resistance

according to EN 60068-2-6 / EN 60068-2-27

EMC immunity/emission

according to EN 61000-6-2 / EN 61000-6-4

Shocks

15 g with pulse duration 11 ms in all three axes

Protection class

IP20

Permitted operating environment

control cabinet or terminal box with minimum
protection class IP54 according to IEC 60529

Permissible installation position

see section Installation position

Approvals

CE, TÜV SÜD