EL6930

15

3.4 Safety parameters

Key figures

EL6930

Lifetime [a]

20

Prooftest Intervall [a]

not required

1)

PFH

1.03E-09

%SIL3

1.03%

PFD

8.23E-05

%SIL3

8.23%

MTTFd [a]

>100

DC

>99%

Performance level

PL e

Category

4

HFT

1

Element classification*

Type A

*) Classification according to IEC 61508-2:2010 (see chapters 7.4.4.1.2 and 7.4.4.1.3)

The EL6930 EtherCAT Terminal can be used for safety-related applications within the meaning of
IEC 61508:2010 up to SIL3 and EN ISO 13849-1 up to PL e (Cat4).

1)

Special proof tests are not required during the entire service life of the EL6930 EtherCAT terminal.

3.5 Dimensions

Width: 12 mm (side-by-side installation)

Height: 100 mm

Depth: 68 mm