4.2.7.1

TwinSAFE group signals

TwinSAFE group inputs

Name

Permitted type

Description

RUN

FB-Out

Standard-In

TRUE:

The function blocks assigned to the TwinSAFE group are
executed. When the input is not linked it is in the TRUE
state

FALSE: All of the TwinSAFE group assigned function blocks are at

a STOP state and thus all associated outputs are in a safe
state.

ERR Ack

FB-Out

Standard-In

All pending errors in the assigned function blocks and in the
TwinSAFE connections are acknowledged by the FALSE->TRUE-
>FALSE signal sequence.