3 pilot operated valve, 4 bellows valve, Value calculation – Bronkhorst IN-FLOW User Manual

Page 14: 1 for gases

Advertising
background image

BRONKHORST HIGH-TECH B.V.

page 14

9.17.022

1.3.3 Pilot operated valve

For high flow rates the pilot operated valve has been designed. A

solenoid driven control valve controls the pressure difference

across a piston, which lifts the main plunger.

1.3.4 Bellows valve

This valve type is a direct driven, low power, solenoid operated control valve. A special design, incorporating

a metal bellows allows for a relatively large orifice opening to be controlled. The design is suited for low

pressure or vacuum applications.

1.4

K

v

-value calculation

This calculation method can be used to determine the K

v

-value of the main orifice of a control valve.

1.4.1 For gases

Determine desired ∆p across valve.

p must be at least 20% of supply pressure, or in closed loop systems, of total pressure difference in loop.

If ∆p is 20-50% of supply pressure, use formula:

K

T

p p

v

vn

n

=

Φ

514

2

ρ

undercritical

If ∆P is 50-100% of supply pressure, use formula:

K

p

T

v

vn

n

=

Φ

257

1

ρ

overcritical

Units:

Φ

vn

= flow [m

n

3

/h]

p

1

= supply pressure [bara]

p

2

= downstream pressure [bara]

p = pressure difference (p

1

- p

2

) [bara]

T = temperature [K]

ρ

n

= density [kg/m

n

3

]

The orifice diameter can be determined by: d= 7.6

K

v

[mm]

P1

pilot valve

pressure

compensating

valve

P2

flowcontrol valve