11 s, 12 f, 13 f – Bronkhorst Multibus User Manual

Page 19

Advertising
background image

BRONKHORST

®

Page 19

Operational instructions for digital multibus instruments

9.17.023

4.10.1 Dual interface operation

When operating a controller (reading measured value and sending setpoint) for proper operation it is important that

the controller gets its setpoint from the right source. Setpoints may come from different sources: analog input, field

bus interface, RS232 interface or may be overruled by close valve or open valve (purge) commands. Therefore it is

important to know what the setpoint source of the controller is. This can be set by means of parameter control mode

(DDE parameter 12).

In some cases it is possible that the setpoint may come from 2 sources at the same time. The last setpoint send will be

valid and send to the controller. This is the case in control mode = 0, when setpoints may come through any field bus

interface or RS232. However, there could be situations where control over the instrument seems impossible. This is

the case when the instrument comes into a safe-state e.g. when field bus communication is disturbed or disconnected.

The valve will be forced to a safe state automatically: closed (NC) or fully open (NO).

In case you want to get control back via RS232 operation, you have to change the control mode. When control mode

gets value 18, safe state will be overruled and sending setpoints via RS232 interface will have effect on the controller

again. ‘Control Mode’ value 18 will be lost after power off and power on of the instrument.

4.10.2 Tuning, test and calibration mode

These are special modes to prepare the instrument for either a tuning, test or calibration action. These modes are used

by Bronkhorst service personnel only and are not meant for customer use.

4.11 S

LAVE

F

ACTOR

float

0…500

RW

N

139

33/1

Depending on the Setpoint/control mode a slave factor can be set.

In master/slave or ratio control the setpoint of an instrument is related to the output signal of another instrument.

100%

factor

slave

al

Outputsign

setpoint

(master)

(slave)

=

Digital instruments offer possibilities for master/slave control via the FLOW-BUS. The output value of any instrument

connected to the FLOW-BUS is automatically available to all other instruments (without extra wiring). When

master/slave control is wanted the instrument can be put in control mode 2 or 13, depending on how the slave factor

should be set (see table above). Through FLOW-BUS an instrument can be told that it should be a slave, who should be

its master (DDEpar. 158 ‘Master Node’) and what should be the slave factor to follow the master with. It is possible to

have more masters and more slaves in one system. A slave can also be a master itself for other instruments.

These options are available for FLOW-BUS or RS232 instruments only.

Output signals from master can be received via FLOW-BUS only.

Slave factors can also be changed via RS232.

Master/slave is meant here for controlling purposes and has nothing to do with master and slave behavior on field bus

networks.

4.12 F

LUID NUMBER

unsigned char

0…7

RW

N

24

1/16

Fluid number is a pointer to the set of calibration parameters. Each selectable fluid has its own set of calibration

parameter values. Fluid number is an unsigned char parameter (DDEpar. 24 ‘Fluid number’) in the range of 0...7, where

0 = fluid1 and 7 = fluid8. Up to 8 fluids can be stored in one instrument. Default value = 0 (fluid 1).

4.13 F

LUID NAME

unsigned char[10]

a…z / 0…9

RW

Y

25

1/17

Fluid name consists of the name of the fluid of the actual selected fluid number. Up to 10 characters are available for

storage of this name. This parameter is secured and read-only for normal users (it is written during calibration at the

factory). Default value is “Air”.

Advertising