Comtech EF Data EQ90 Series User Manual

Page 30

Advertising
background image

Operation

EQ90 Amplitude Equalizer

3-6

Rev. 2

R

R

EQ6

C

IN

OUT

DELAY

L

R

R

EQ7

C

IN

OUT

DELAY

L

R

R

SLP
ADJ

BYPASS

LVL MON

GAIN
ADJ

EQ10

C

IN

OUT

DELAY

L

R

R

EQ9

C

IN

OUT

DELAY

L

R

R

EQ8

C

IN

OUT

DELAY

L

R

R

EQ5

C

IN

OUT

DELAY

L

R

R

EQ4

C

IN

OUT

DELAY

L

R

R

EQ2

C

IN

OUT

DELAY

L

R

R

EQ1

C

2

3

4

5

6

8

7

1

IN

OUT

DELAY

L

R

R

EQ3

C

IN

OUT

DELAY

L

Figure Chapter 3-3. Equalizer Module

Table Chapter 3-3. Equalizer Module Control Functions

Item

Nomenclature

Function

1

R Switch

Used to adjust the amplitude response.
(Refer to Figure Chapter 3-7 for the signal pattern.)

2

L Switch

Used to adjust the delay peak magnitude.
(Refer to Figure Chapter 3-6 f or the signal pattern.)

3

C Switch

Used to adjust the delay peak center frequency. (Refer to Figure Chapter 3-5
for the signal pattern.)

4

IN/OUT Switch

Used to insert an equalizer delay section to, or remove from, the signal path.

5

R Switch

Used to adjust the amplitude response. (Refer to Figure Chapter 3-8 for the
signal pattern.)

6

GAIN ADJ Potentiometer

Used to set the IF output signal gain level (nominally 15 dB).

7

SLP ADJ Potentiometer

Used to provide

±

3 dB amplitude slope equalization.

8

BYPASS/LVL MON Switch

Used to activate the IF output signal level monitoring function. The minimum
signal level required to avoid an alarm condition is -20 dB. In the BYPASS
position, the signal level is not monitored. However, a power supply failure
will result in an alarm condition.


Advertising