Daktronics AB-1600-1.5,2.5 User Manual

Page 33

Advertising
background image

Electrical Installation

3-7

Branch Circuit Grounding
A grounding electrode at separate structures/displays shall not be required where only one
branch circuit supplies the structure and the branch circuit includes an equipment-grounding
conductor for grounding the non-current-carrying parts of all equipment.

Power Installation
There are two considerations for power installation; installation with ground and neutral conductors
provided and installation with only a neutral conductor provided. These two power installations
differ slightly, as described in the following paragraphs:

Installation with Ground and Neutral Conductors Provided
For this type of installation, the power cable must contain an isolated earth-ground conductor.
Under this circumstance, do not connect neutral to ground at the disconnect or at the display.
This would violate electrical codes and void the warranty. Use a disconnect so that all hot lines
and neutral can be disconnected. Refer to Figure 28 for installation details. The National
Electrical Code requires the use of a lockable power disconnect within sight of or at the
display.

Installation with Only a Neutral Conductor Provided
Installations where no grounding conductor is provided must comply with article 250-
32 of the National Electrical Code. If the installation in question meets all of the
requirements of article 250-32, the following guidelines must be observed:

Connect the grounding electrode cable at the local disconnect, never at the display power
termination panel.

A disconnect that opens all of the ungrounded phase conductors should be used.

The neutral and the ground conductors should be bonded in the display power termination
panel.

Refer to Figure 29 for installation details.

Figure 28: Installation with Ground and Neutral Conductor Provided

Advertising