Daktronics AB-1600-1.5,2.5 User Manual

Page 64

Advertising
background image

Maintenance & Troubleshooting

4-20

DS13

Test Mode

DS14

Taxi Command Received (Will Flash with Data Received)

DS15

Sign is Blank

DS16

Sign Forced Blank – Signal Loss or Fan Failure

DS17

On=Fans On, Blinking=Fan Failure, Off=Fans Off

DS18

Heartbeat

DS19

N.C.

Receiver Board Miscellaneous LEDs and Jumpers
DS9

Power LED should be ON

DS20

Violation LED – If ON indicates a problem with signal format
or configuration

W1

Jumper – Test Pattern, Bottom=ON / Top=OFF

W2

Jumper – Fan Sensing, Top=Enable / Bottom=Disable


Output Card Connectors
Connector

Function

J2, J3, J6, J7

Data 1 Output – All connectors XMIT same data

J4, J5, J8, J9

Data 2 Output – All connectors XMIT same data

Output Card DS1-DS4 Indicator LEDs
LED

Function

DS1

Should blink when data is received from Venus 7000

DS2

Should blink when data is received from Venus 7000

DS3

Should blink when data is received from Venus 7000

DS4

All DS4 LEDs in data distributor will light and then count
sequentially through card addresses from 0 to 15.


Output Card Miscellaneous LEDs and Switches
DS5

Power LED should be ON

S1

Board Address – Set in sequential order starting at 0.
Four output cards would be set 0, 1, 2, 3. Not 1, 2, 3, 4.