Flowserve Type R User Manual

Page 6

Advertising
background image

R and RX SLURRY Pump USER INSTRUCTIONS ENGLISH

71569242 03-11 (E)

Page 6 of 54

®

HOT (and cold) PARTS

If hot or freezing components or auxiliary heating
supplies can present a danger to operators and
persons entering the immediate area action must be
taken to avoid accidental contact. If complete
protection is not possible, the machine access must be
limited to maintenance staff only, with clear visual
warnings and indicators to those entering the
immediate area. Note: bearing housings must not be
insulated and drive motors and bearings may be hot.

If the temperature is greater than 80 ºC (175 ºF) or
below -5 ºC (20 ºF) in a restricted zone, or exceeds
local regulations, action as above shall be taken.

HAZARDOUS LIQUIDS

When the pump is handling hazardous liquids care must
be taken to avoid exposure to the liquid by appropriate
siting of the pump, limiting personnel access and by
operator training. If the liquid is flammable and/or
explosive, strict safety procedures must be applied.

Gland packing must not be used when pumping
hazardous liquids.

PREVENT EXCESSIVE EXTERNAL

PIPE LOAD
Do not use pump as a support for piping. Do not mount
expansion joints, unless allowed by Flowserve in
writing, so that their force, due to internal pressure, acts
on the pump flange.

ENSURE CORRECT LUBRICATION

(See section 5, Commissioning, startup, operation and
shutdown

.)

START THE PUMP WITH OUTLET

VALVE PARTLY OPENED
(Unless otherwise instructed at a specific point in the
User Instructions.)
This is recommended to minimize the risk of
overloading and damaging the pump motor at full or
zero flow. Pumps may be started with the valve further
open only on installations where this situation cannot
occur. The pump outlet control valve may need to be
adjusted to comply with the duty following the run-up
process. (See section 5, Commissioning start-up,
operation and shutdown

.)

NEVER RUN THE PUMP DRY

INLET VALVES TO BE FULLY OPEN

WHEN PUMP IS RUNNING
Running the pump at zero flow or below the
recommended minimum flow continuously will cause
damage to the pump and mechanical seal.

DO NOT RUN THE PUMP AT

ABNORMALLY HIGH OR LOW FLOW RATES
Operating at a flow rate higher than normal or at a flow
rate with no back pressure on the pump may overload the
motor and cause cavitation. Low flow rates may cause a
reduction in pump/bearing life, overheating of the pump,
instability and cavitation/vibration.

1.6.4 Products used in potentially explosive

atmospheres

Measures are required to:

 Avoid excess temperature

 Prevent build up of explosive mixtures

 Prevent the generation of sparks

 Prevent

leakages

 Maintain the pump to avoid hazard

The following instructions for pumps and pump units when
installed in potentially explosive atmospheres must be
followed to help ensure explosion protection. For ATEX,
both electrical and non-electrical equipment must meet
the requirements of European Directive 94/9/EC. Always
observe the regional legal Ex requirements eg Ex
electrical items outside the EU may be required certified
to other than ATEX eg IECEx, UL.

1.6.4.1 Scope of compliance

Use equipment only in the zone for which it is

appropriate. Always check that the driver, drive coupling
assembly, seal and pump equipment are suitably rated
and/or certified for the classification of the specific
atmosphere in which they are to be installed.

Where Flowserve has supplied only the bare shaft
pump, the Ex rating applies only to the pump. The party
responsible for assembling the ATEX pump set shall
select the coupling, driver and any additional equipment,
with the necessary CE Certificate/ Declaration of
Conformity establishing it is suitable for the area in which
it is to be installed.

The output from a variable frequency drive (VFD) can
cause additional heating affects in the motor and so, for
pumps sets with a VFD, the ATEX Certification for the
motor must state that it is covers the situation where
electrical supply is from the VFD. This particular
requirement still applies even if the VFD is in a safe area.

1.6.4.2 Marking
An example of ATEX equipment marking is shown
below. The actual classification of the pump will be
engraved on the nameplate.

Advertising
This manual is related to the following products: