Replacing Filter in Spool Valve Cover
1. Make sure the valve is bypassed or in a safe condition.
2. Disconnect the power and air supply to the unit.
3. Remove the spool cover by removing the screw and

sliding the cover assembly backwards until the tab is
clear of the slot. The sheet metal cover may be
removed and cleaned with a brush or by blowing out
with compressed air (Figure 13).

4. Remove the O-ring from around hydrophobic filter

element and set aside (Figure 12).

5. Remove the molded filter element by pulling straight

out of chamber cover vent piece.

6. Place new molded filter element into the chamber cover

vent piece. This element provides part of the track to
secure the O-ring in the next step.

7. Install O-ring into base of chamber cover vent piece as

shown in Figure 12.

8. Place spool valve shroud onto spool valve cover.
9. Place the spool valve cover assembly in place by

setting it on the ramp and sliding it until the tab seats
in the slot, as shown in Figure 13, and secure with
No. 8-32 screw.

Regulator

The regulator reduces the pressure of the incoming
supply air to a level that the driver module can use.

Replacing Regulator
1. Make sure valve is bypassed or in a safe condition.
2. Disconnect the power and air supply to the unit.
3. Remove the main cover and unscrew the regulator

from the interface plate, exercising caution not to
damage the collector board (Figure 19).

4. Verify that the O-rings are in place on the base of the

new regulator.

5. Replace the regulator by threading into the port on the

interface plate.

Internal Coalescing Filter

The internal coalescing filter ensures that supply air is
clean and dry before it gets to the regulator. Because the
air has already been filtered before this point, the element
should not require extended maintenance.

Replacing Input Filter Element (Figure 19)
1. Make sure valve is bypassed or in a safe condition.
2. Disconnect the power and air supply to the unit.
3. Remove the main cover and remove collector board by

disconnecting the wiring and removing three screws
that attach it to the housing. Each cable has its own
unique connector to prevent mistakes in reconnecting.

Figure 12: Spool Valve Cover Assembly

Figure 13: Spool Valve Cover Assembly

O-ring

Hydrophobic
Filter

Spool
Valve
Cover

Spool
Valve
Shroud

Screw

Spool Valve Cover