Speaker Loop Return Lines

Terminate the central amplifier speaker loops to be monitored by the ADM on connectors TB3, TB6,
TB9, TB12, TB15, and TB18. Typically, this connection is made to the last speaker on the circuit so
that the entire loop is monitored. These connections are not polarity-sensitive.

N

OTE

: The conductors terminated on TB3, TB6, TB9, TB12, TB15, and TB18

should be twisted pairs.

Table 9. Circuit Relationships

Function
Ckt. No.

Central Amplifier

Audio Distribution

Speaker Loop

Interfaces

Ground Fault

Detection Control

Central Amplifier

Failure Contact

1

TB2-1 (AMP1

L1)

TB2-2 (AMP1

L2)

TB3 (SPKR

1) J4 (GF1) TB1 (CCIN1)

2

TB5-1 (AMP2

L1)

TB5-2 (AMP2

L2)

TB6 (SPKR

2) J5 (GF2) TB4 (CCIN2)

3

TB8-1 (AMP3

L1)

TB8-2 (AMP3

L2)

TB9 (SPKR

3) J6 (GF3) TB7 (CCIN3)

4

TB11-1 (AMP4

L1)

TB11-2 (AMP4

L2)

TB12 (SPKR

4) J7 (GF4) TB10 (CCIN4)

5

TB14-1 (AMP5

L1)

TB14-2 (AMP5

L2)

TB15 (SPKR

5) J8 (GF5) TB13 (CCIN5)

6

TB17-1 (AMP6

L1)

TB17-2 (AMP6

L2)

TB18 (SPKR

6) J9 (GF6) TB16 (CCIN6)

Table 9 shows the relationship between the connectors and headers for each of the six circuits the ADM
supports. It includes the component’s designation and the label printed on the Distribution/Monitor
PCBA, where applicable.

For example: audio for circuit 1’s amplifier input is passed from the AZI PCBA to terminal block TB2
(labeled AMP1

L1 and AMP1

L2). The speaker loop return line for this circuit is via TB3 (labeled

SPKR

1) and it includes ground fault detection control via header J4 (labeled GF1). The related contact

closure input is via TB1

(labeled

CCIN1).

After all terminations have been made, apply power to the equipment, and adjust reference level

R88

and

tone level

R75

as described in the “Maintenance” section.