2 set-up, 3 nmt start-up (od index 1f80h), 1 slave only (default) (od index 1f80h = 0) – ifm electronic JN2100 v.2.2.0 User Manual

Page 8: 2 nmt start command (od index 1f80h = 2), 3 autostart (od index 1f80h = 8)

Advertising
background image

Inclination sensor JN

8

● Status and error indication via LED

● In addition to the basic CANopen functions there are other manufacturer and

profile-specific features:

– setting of the node ID and the baud rate via OD

– configurable limit frequency (digital filter)

7.2 Set-up
The CANopen standard CiA DS-301 defines three possible states for sensor

nodes.
Pre-Operational

The pre-operational state is used to set the sensor parameters or as standby

mode. In the pre-operational state no process data (PDO messages) can be

transmitted.
Operational

The operational state is used to exchange the process data while in operation. In

the operational state all communication services are carried out.
Stopped

The stopped state is used for network management; only NMT messages are

possible.
The master or network manager can request the sensor via NMT messages to

change the state accordingly. This allows almost complete separation of redundant

or faulty sensors from the bus.
7.3 NMT start-up (OD index 1F80h)
The sensor has a selectable start performance. The following three options can be

selected under the index 1F80h:
7.3.1 Slave Only (default) (OD index 1F80h = 0)
The sensor starts in the pre-operational state (0x00h).
7.3.2 NMT start command (OD index 1F80h = 2)
This command is used for CAN bus networks without NMT master. If the sub-

index 0x02h is selected, the sensor starts after a new start as NMT master in the

operational state and sets the other network participants from the pre-operational

into the operational state.
7.3.3 Autostart (OD index 1F80h = 8)
If this command is written under the sub-index 0x08h, the sensor starts

automatically in the operational state after a new start.