Operating principle

The by-bass valve contains a
non-return obturator connected to a
contrast spring. When the fixed
setting pressure is reached, the
valve obturator gradually opens,
recirculating the flow in proportion
to the closing of the thermo-electric
valves and maintaining a constant
differential pressure in the manifold
circuit.

Construction details

The differential bypass assemby
features a fixed setting that cannot
be changed because it does not
contain accessible adjustment
parts. The small, compact size and
offset connections makes this kit
particularly easy to mount after
installing thermo-electric valves on
the manifold. It does not require a
larger or deeper zone box than
those used for normal manifolds.

Hydraulic characteristics

Bypass differential pressure:

25 kPa (2500 mm w.g.)

500

10000

1000

100

G (l/h)

ΔP (mm w.g.)

2000

5000

120

140

160

180

200

250

300

350

400

450

9000
8000
7000

6000

1200

1400

1600

1800

2500

3000

3500

4000

4500

100

10

20

50

90
80
70

60

12

14

16

18

25

30

35

40

45

ΔP (kPa)

1000

600

700

800

900

1200

1400

1600

1800

2000

Technical specification

Materials: - body:

brass EN 12164 CW614N

- nuts:

brass EN 12165 CW617N

- Ø 18 pipe with plate:

copper

- check valve obturator:

PA

- spring:

stainless steel

- seals:

EPDM

- gaskets:

asbestos-free fibre

Medium:

water, glycol solutions

Max. percentage of glycol:

30%

Max. working pressure:

10 bar

Temperature range:

-10–110°C

Fixed setting pressure:

25 kPa (2500 mm w.g.)

Connections:

1/2” M x 1/2” M

Dimensions

A

B

137

÷

150

C

A

1/2"

C

1.4"

B

1/2"

Code

22090

Weight (lb)

.75

Off-centre bypass assembly with fixed setting

Function

The distribution circuits of the heating fluid in radiant panel systems may be totally or partially shut off by closing the
thermoelectric valves inside the manifolds.
When the flow decreases, the differential pressure inside the circuit may rise to levels that could cause problems with noise,
high rates of fluid speed, mechanical erosion and hydraulic imbalance of the system itself. The differential bypass kit for
manifolds maintains the pressure of the flow and return manifold circuits in balance if the flow changes.
The valve can be quickly connected to the manifolds, reducing overall size to a minimum.

Product range

Part #22090 Off-centre bypass assembly with fixed setting

Size 1/2” x 1/2”

Advertising