Fuel supply + manifold pressure checking, Installation – Montigo 34FID - Linear User Manual

Page 21

Advertising
background image

Page 21

XG0514-150204

I-Series Indoor Gas Fireplace

Installation

Fuel Supply + Manifold Pressure Checking

It’s imperative that you verify that the supply pressure to your

appliance is adequate and that the valve is supplying the

correct pressure to the pilot and main burner. The pilot burner

operates at line pressure and may need further adjustment.

The valve outlet pressure is set by the manufacturer of the

valve but should be verified upon install. Follow the following

steps to perform this system check. Inlet pressure must be

checked with fireplace burning.

1). Remove the 2 screws from the Valve Mounting Bracket so that

the valve can be swung away from the unit. The Shut off lever

needs to be in the “off” position to be able to swing the valve out

of the valve control box.

Figure 41 Sec.4

2) . Using a slotted screw driver, loosen the Manifold Tap on the

valve front.

Figure 42 Sec.4

3). Attach a silicon hose to over top of the pressure tap on the

valve face. Connect the hose to a manometer.

4). The emergency Shut-off valve needs to be placed in the

“ON” position, see section for operation. The pressure tap on the

left is to be used to measure supply line pressure. Refer to the

specifications at the beginning of this manual for the gas pressure

specs. Be sure to close and leak test all potential leak areas prior

to closing in the install. Using the remote, turn the main burner on.

Check the inlet pressure and the manifold pressure on high and

low. Refer to specification sheet for acceptable values. Remove

rubber tubes, close taps and check for leaks. Close emergency

shut-off valve reinstall the valve mounting bracket. Make sure

wires and pilot gas lines are not pinched or kinked. Check pilot

gas line for leaks.

Figure 43 Sec.4

Manifold

Fuel Supply

Figure 44 Sec.4

Advertising