23 | SAM-e Installation

Pressurized Plumbing without External Separator


Note: The SAM-e header functions as a steam separator, therefore an external steam
separator is not required.















• Steam components in grey provided by Nortec.
• Tap steam from top of pressurize steam main to avoid excess condensate.
• Condensate from SAM-e to be returned to atmospheric floor drain.

When pressurized steam enters SAM-e, pressure drops down to almost atmospheric pressure.
Therefore, it must be drained atmospherically, and the use of a condensate pump (rated for 212ºF)
must be used to raise condensate to a higher elevation.

1” Air Gap

Drain

Strainer

Manual Shut-Off
Valve (By Others)

Pressurized
Steam Main

6” min.

Return to non-pressurized
floor drain

Pressurized condensate
return main

Tap steam from top of
pressurized steam main