Mini sam-e with pressurized steam, Mini sam-e pressurized with external separator – Nortec SAM-e User Manual

Page 29

Advertising
background image

SAM-e Installation | 26

Mini SAM-e with Pressurized Steam

Mini SAM-e Pressurized with External Separator



• Steam components in grey provided by Nortec.
• Tap steam from top of pressurize steam main to avoid excess condensate.
• Condensate from separator to be returned to pressurized condensate main.
• Condensate from SAM-e to be returned to atmospheric floor drain.

When pressurized steam enters SAM-e, pressure drops down to almost atmospheric pressure.
Therefore, it must be drained atmospherically, and the use of a condensate pump (rated for 212ºF)
must be used to raise condensate to a higher elevation.


Strainer

Manual Shut-Off
Valve (By Others)

Steam Main

F & T Steam Trap

Separator

Actuator & Valve

Pressurized condensate
return main

1” Air Gap

Drain

Steam from top of main

Manual Shut-Off
Valve (By Others)

6” min.

6” min

Return to non-pressurized
condensate return main

Duct Width

Duct

Height

Duct Floor

Mounting
bracket