37 | SAM-e Installation

SE Steam Line

Table 3: SE Steam-Line

Unit

No. of

Steam

Outlets

Steam
output

[ lb ]

MED-L copper

tube nominal

steam line size

Stainless steel

tube diameter

(wall thickness

0.065”)

Steam loss

per foot in

condensation

[ lb/ft ]

Steam line

maximum

equivalent

length

SE 050

1

50

1-1/2”

1-3/4”

0.11

37 ft

SE 100

1

100

1-1/2”

1-3/4”

0.11

90 ft

SE 175

1

175

3”

3”

0.16

90 ft

SE 250

1

250

3”

3”

0.16

180 ft

SE 375

1

375

4”

4”

0.22

180 ft

SE 575

1

575

4”

4”

0.22

220 ft

SE 750

2

750

2 x 4”

2 x 4”

0.44

260 ft

SE 1050

2

1050

2 x 4”

2 x 4”

0.44

260 ft


• Based on 3” duct static pressure.

• Maximum duct static pressure for SE is 12” w.c.