37 | SAM-e Installation
SE Steam Line
Table 3: SE Steam-Line
Unit
No. of
Steam
Outlets
Steam
output
[ lb ]
MED-L copper
tube nominal
steam line size
Stainless steel
tube diameter
(wall thickness
0.065”)
Steam loss
per foot in
condensation
[ lb/ft ]
Steam line
maximum
equivalent
length
SE 050
1
50
1-1/2”
1-3/4”
0.11
37 ft
SE 100
1
100
1-1/2”
1-3/4”
0.11
90 ft
SE 175
1
175
3”
3”
0.16
90 ft
SE 250
1
250
3”
3”
0.16
180 ft
SE 375
1
375
4”
4”
0.22
180 ft
SE 575
1
575
4”
4”
0.22
220 ft
SE 750
2
750
2 x 4”
2 x 4”
0.44
260 ft
SE 1050
2
1050
2 x 4”
2 x 4”
0.44
260 ft
• Based on 3” duct static pressure.
• Maximum duct static pressure for SE is 12” w.c.