SAM-e Installation | 56

Troubleshooting

Steam tubes discharge water:

1 Steam supply pipe is not insulated.
2 Steam supply pipe not properly drained or sloped.
3 Manifold or adapter condensate drain is clogged or malfunctioning.
4 Excessive back-pressure in condensate drain pipe (due to pressure in secondary condensate

drain); must be piped to non-pressurized condensate return.

5 Primary and secondary condensate drains are both joined together.
6 Condensate line has been routed too high (causing static back pressure).

Maintenance


Inspect SAM-e at start-up.
1 For humidifier maintenance schedule, refer to Installation, Operation, and Maintenance

Manual for your humidifier.

Spare Parts

Kit Part #

Kit description

Quantity in Kit

1503812

SAM-e coupling seal for steam tubes (1 per tube)

1

2546662

Insertion stop (1 per tube) (Galvanized)

10

2578156

Insertion stop (1 per tube) (Stainless Steel)

10

2546665

5/16” Locknuts, bolts, washers (Galvanized)

10

2546668

5/16” Locknuts, bolts, washers (Stainless Steel)

10

2546667

1/4" bolts, washers (1 per tube) (Galvanized)

10

2578157

1/4" bolts, washers (1 per tube) (Stainless Steel)

10

2538346

SAM-e insulated tube strapping

1

2538347

SAM-e insulated header strapping

1

2538344

SAM-e insulated dual-inlet header strap (for second inlet)

1