SAM-e Installation | 28
Mini SAM-e Condensate Pump Plumbing
When pressurized steam enters Mini SAM-e, pressure drops down to almost atmospheric pressure.
Therefore, it must be drained atmospherically, and the use of a condensate pump (rated for 212ºF)
must be used to elevate condensate to a higher point.
6” min.
Condensate Pump
(By Others)
Pressurized condensate
return main
Pressurized Steam
from Valve
Advertising