Electrode steam-line – Nortec SAM-e User Manual

Page 38

Advertising
background image

35 | SAM-e Installation

Electrode Steam-Line

Table 1: Electrode Steam-Line

Humidifier

Steam
output

[ lb ]

MED-L copper

tube nominal

steam line size

Stainless steel

tube diameter

(wall thickness

0.065”)

Steam loss per

foot in

condensation

[ lb/ft ]

Steam line

maximum

equivalent

length

RH Duct 120V

5

3/4"

7/8”

0.06

8 ft

RH Duct 240V

10

3/4"

7/8”

0.06

15 ft

NH 005

5

3/4"

7/8”

0.06

7 ft

NH 010

10

3/4"

7/8”

0.06

12 ft

NH 020

20

3/4"

7/8”

0.06

17 ft

NH 030

30

3/4"

7/8”

0.06

22 ft

NH 050

50

1-1/2”

1-3/4"

0.11

43 ft

NH 075

75

1-1/2”

1-3/4"

0.11

47 ft

NH 100

100

1-1/2”

1-3/4"

0.11

50 ft

NH 150 (2 outlets)

150

2 x 1-1/2”

1-3/4"

0.11

47 ft

NH 200 (2 outlets)

200

2 x 1-1/2”

1-3/4"

0.11

50 ft

• Based on 3” duct static pressure.

• Maximum duct static pressure for electrode steam units is 6” w.c.

• A fill cup extension kit can be used on NH to overcome higher duct static pressure, or for

longer steam line runs. (Consult factory).