SAM-e Installation | 34

Plumbing

Pressurized SAM-e

For pressurized steam line installation instructions, refer to LiveSteam Steam Injection
Humidifier Installation Manual
.

Atmospheric SAM-e Steam Lines

Guidelines

1 Nortec steam hose should only be used on short steam runs of less than 10 feet.

2 Ensure that no condensate produced in steam line will remain trapped. Steam naturally

flows upward and condensate naturally flows downward.

3 See material recommended for use in below chart. To eliminate metal corrosion, Nortec

does not recommend the use of steel piping.

4 Consult below charts for steam and condensate sizing guidelines when using steam

distributors.

5 Be sure to include fitting equivalent lengths in total steam run lengths (see below).

In general, match steam-line size to outlet size of distributor.

When using an SETC with less than 15 psig steam supply pressure, a reducer (Nortec part
number 2526110 – 3” to 1.5” reducer or 2526111 – 4” to 3” reducer) is required to
prevent over-sizing of steam lines.

All steam lines should be insulated with at least 1”-thick steam insulation.