Atmospheric sam-e condensate drainage – Nortec SAM-e User Manual

Page 43

Advertising
background image

SAM-e Installation | 40

Atmospheric SAM-e Condensate Drainage

1 SAM-e condensate outlet connection is male 3/4”-NPT.

2 Condensate from SAM-e must be plumbed to a P-trap. Trap must have center-to-center

height of at least 8”, or 2” more than duct static pressure, whichever is greater. Refer to
typical installation drawings.

3 Condensate from P-trap should drain into a funnel with air-gap prior to entering building

drain.

4 Condensate exits at 212°F (100°C). Local codes may require use of a drain water

cooler (Nortec part number 1710020 - electronic drain water cooler or 1710010 – self-
actuated drain water cooler). Refer to installation manual that accompanies drain water
cooler for plumbing details.

5 When collecting condensate, ensure that each device has an air-gap prior to entering the

condensate collection system. Failing to incorporate an air-gap may cause backpressure
on SAM-e and result in poor performance.

6 Some humidifiers allow distributor condensate to be returned to the unit. Refer to

humidifier manual for details.

7 For systems using condensate pumps, a P-trap and air-gap are still required at SAM-e

outlet. Never connect SAM-e directly to a pressurized drain line.

Advertising