7 | Installation

Location

Mount on a suitable wall or vertical surface. Do not sit the unit on the floor. Allow clearances
required for plumbing and electrical connections. Clearance dimensions shown are for
reference only and are the minimum required for maintenance of the humidifier. Consult local
and national codes before final location and installation. Nortec does not accept responsibility
for installation code violations.

Install only in areas with ambient temperature 41-104°F (5 – 40°C) relative humidity

5 - 95%.

When possible install below the steam distributor. Take care to provide proper steam line

routing and proper condensate traps.

DO NOT locate the humidifier any further then absolutely necessary from the steam

distributor location as net output will be reduced as a result of heat loss through the steam
line.

When possible, mount the RH2 humidifier at a height convenient for servicing.







Figure 4: Mounting Location / Clearance

Side clearance

for space models

only, see table

36 in. (92 cm)

in. ront learance

duct model

m

f

c

Additional front clearance

for space models,

see table

24 in.(61 cm)

Min Height

Mount Humidifier

Level

As Close as

Possible to Steam

Distributor

5-95%

Overhead clearance

for space models

only, see table

Humidifier Output lb (kg)

Side in. (cm)

<4 (1.8)

12 (30)

12 (30)

6 (2.7)

16 (40)

18 (46)

8 (3.6)

18 (46)

18 (46)

7 ft (2.1 m)
min. Height

for space

models only.

36 (92)

42 (107)
48 (120)

Additional Clearance for Space Models Only

Overhead in. (cm)

Front in. (cm)

Note: Do not mount on hot surfaces, where freezing can occur, vibrating surface, or floor.