13 | Installation




Figure 10: Main Steam Line Requirements

MAIN RULES FOR ATMOSPHERIC STEAM LINES

Steam lines must not have any restrictions which could result in back pressure.

Follow recommended materials, size and length, see tables.

Slope the steam lines.

Insulate with 1.0 in. (2.5 cm) pipe insulation

Trap condensate (Use full size ‘T’ for Traps)

Do not over tighten hose clamp at cylinder steam outlet. The maximum torque is 12

in-lbs.

Support steam line so weight is not on cylinder.

Condensate traps must be a minimum of 6 in. (15 cm) in height or duct static

pressure + 2 in. (5 cm), whichever is greater.

Trapping by P-trap or pigtail. Support line as necessary to ensure it remains free of

kinks.

Steam Direction

Steam Direction

Steam

Direc

tion

2 in.
(5 cm)

1 ft (30 cm)

1ft (30 cm)

0.5 in.
(12 mm)

10 Degrees

2 Degrees

Use Appropriate Slope

Insulate Pipe

1 in. (2.5 cm) pipe

insulation