Installation | 18

Space Humidification Control Location

These instructions apply to the RH2 Space and the RH2 Duct with Remote Blower Pack.

Figure 17: Control Location (In-Space Humidification)

Space Humidification

1 Humidity Control – Can be Modulating or On/Off humidistat

o Locate in room being humidified but not in discharge zone of blower pack.
o Mount in area representative of room humidity (draft, doorways, sunlight, or

overhang such as a shelf can affect reading).

2 High Limit Humidistat (not shown)

o Install an On/Off High Limit Humidistat in an area representative of room humidity.

3 Outdoor Temperature Sensor (not shown)

o Mount outside in area representing air temperature.













Note: Regardless of selecting on/off or modulating control method,

Nortec humidifiers must have a closed circuit across its on/off security

loop control terminal to operate. Nortec highly recommends the use of a

high limit humidistat and an air proving switch in series for this function.