Troubleshooting| 52

Table 8: Troubleshooting RH2 Faults (Continued)

Yellow LED

System Detected

Cause

Corrective Action(s)


2 flashes

No Current
Fill valve activated for
long time but high water
level not reached.
Fill should be faster than
1” per minute.

1 Drain valve leaking or stuck

open

1 Clean drain valve or replace

(see maintenance chapter)

2 Water shut off valve closed

2 Open shut off valve

3 Fill Valve strainer blocked

3 Clean out strainer on fill valve

inlet.

4 High system back pressure

4a Check for kinked hose
4b Check for proper

condensate removal (see
installation chapter)

4c Install fill cup extension

5 High water sensor not

connected

5 Check that cylinder plug with

white marker is connected to
short electrode with a plastic
well around it and to control
board.

6 Low water conductivity

6a Check if potable water

supplied to unit, not treated
water (RO or DI) .

6b Check conductivity of water.

If less than 150 µS/cm.

6c Add 1/4 teaspoon of salt to

fill cup and restart unit.

3 flashes

No Current, High Water
Water level at top of
cylinder with no current

1 Primary wire not looped

through current transformer.

1 Open disconnect, rewire

primary wire through current
transformer.

2 High water sensor plug is on

an electrode pin.

2 Install high water senor plug

on cylinder pin with shroud
around it.

3 Cylinder plugs installed

incorrectly

3 Check that cylinder plugs

colors match markers next to
electrodes on cylinder and
that white marked cylinder
plug is connected to short
electrode located in plastic
well.

4 flashes

Cylinder Spent
Electrodes covered with
scale.

1 Cylinder electrodes are

covered with scale and
humidifier cannot meet
demand

1 Replace cylinder with same

model number (see
maintenance chapter).

In order to clear “spent

cylinder” fault codes,
externally powered
modulating controllers will
have to be turned off before
power cycling the unit.