51 | Troubleshooting

RH2 Faults

The self-diagnostic system built into the RH2 is continually monitoring the operation of the
humidifier. When an abnormal condition occurs that cannot be self-corrected by the software
the RH2 will turn off power to the cylinder, drain the cylinder, and annunciate the fault using the
yellow status LED.

LED Flash Sequence

To differentiate between different fault conditions the yellow LED is flashed in different
sequences. Table 8 lists the fault sequences that can be displayed, their meaning, possible
cause and suggested corrective actions.

Clearing a Fault

Check the flash sequence against the list of fault messages and take any necessary actions

to correct the cause(s) as outlined in Table 8: Troubleshooting RH2 Faults.

Power cycle the humidifier with the On/Off switch waiting 10 seconds between turning it off

and on. If an externally powered 0-10V controller is used, it must be turned off prior to
clearing the fault.

Table 8: Troubleshooting RH2 Faults

Yellow LED

System Detected

Cause

Corrective Action(s)

1 flash

Excess Current
Current has exceeded
130% of max

1 Drain blocked water over

concentrated

1 Clean the drain line

2 Drain solenoid not energized,

water over concentrated

2 Check and correct wiring to

drain valve.

3 Filling too fast, fill valve

damaged and leaking

3 Replace the fill valve

4 Filling too fast, wrong fill valve 4 Check for correct fill valve in

parts list, replace if incorrect

5 Water supply too conductive

5a Contact Nortec

representative for
recommendation on alternate
cylinder

5b Change the water supply

6 Humidifier short cycling

6a Check if high limit or other

On/Off control is cycling
On/Off in less than 5
minutes. Check location and
setting of high limit.

6b Reduce the output by

turning down the capacity
potentiometer.

7 Wrong cylinder installed

7 Install correct cylinder model

8 Cylinder Spent but not

detected by software

8 Replace the cylinder (see

maintenance chapter)

9 Condensate from other

source

9 Remove condensate returns

other than from steam line.

10 Back pressure

10 Eliminate back pressure