Air for combustion and ventilation – Desa FPVF33NRA User Manual

Page 7

Advertising
background image

www.desatech.com

113109-01D

7

1. Determine the volume of the space (length

x width x height).

Length x Width x Height =__________cu. ft.
(volume of space)

Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 560 cu. ft.
(volume of space)

If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.

. Multiply the space volume by 0 to determine

the maximum Btu/Hr the space can support.

________ (volume of space) x 0 = (Maxi-
mum Btu/Hr the space can support)

Example: 560 cu. ft. (volume of space) x 0
= 51,200 (maximum Btu/Hr the space can
support)

3. Add the Btu/Hr of all fuel burning appliances

in the space.

Vent-free fireplace

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________ Btu/Hr

Gas fireplace logs

__________ Btu/Hr

Other gas appliances* + ________ Btu/Hr

Total = ________ Btu/Hr

* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.

Example:

Gas water heater _____________ Btu/Hr

Vent-free fireplace + _____________ Btu/Hr

Total

= ____________ Btu/Hr

4. Compare the maximum Btu/Hr the space

can support with the actual amount of
Btu/Hr used.

_______ Btu/Hr (maximum the space can
support)

_______ Btu/Hr (actual amount of Btu/Hr
used)

Example: 51,200 Btu/Hr (maximum the

space can support)

73,000 Btu/Hr (actual amount of
Btu/Hr used)

The space in the above example is a confined
space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can sup-
port. You must provide additional fresh air. Your
options are as follows:

40,000
33,000
73,000

AIR FOR COMbUSTION

AND VENTILATION

Continued

Figure 3 - Ventilation Air from Inside

Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills

Into Adjoining Room,

Option 2

Ventilation

Grills

Into Adjoining

Room,

Option 1

12"

12"

A. Rework worksheet, adding the space of an

adjoining room. If the extra space provides an
unconfined space, remove door to adjoining
room or add ventilation grills between rooms.
See Ventilation Air From Inside Building.

B. Vent room directly to the outdoors. See

Ventilation Air From Outdoors, page 8.

C. Install a lower Btu/Hr fireplace, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support, the space is an
unconfined space. You will need no additional
fresh air ventilation.

WARNING: If the area in which

the fireplace may be operated

is smaller than that defined as

an unconfined space or if the

building is of unusually tight

construction, provide adequate

combustion and ventilation air by

one of the methods described in

the National Fuel Gas Code, ANSI

Z223.1/NFPA 54 Section 5.3 or

applicable local codes.

vENTILATION AIR

Ventilation Air From Inside Building
This fresh air would come from an adjoining un-
confined space. When ventilating to an adjoining
unconfined space, you must provide two perma-
nent openings: one within 1" of the ceiling and
one within 12" of the floor on the wall connecting
the two spaces (see options 1 and 2, Figure 3).
You can also remove door into adjoining room
(see option 3, Figure 3). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3,
Air for Combustion and Ventilation
for required
size of ventilation grills or ducts.

Advertising